IDX SH2
Tagline: High Standards, High Stability, High Safeguard, Green-Tech & Energy-Saving, High Availability, High Security
- Designed according to Tier4 Standards, Started operating since 2008;
- Housed in a separate 5-floor building, offering 9,000 m2 floor area in total;
- Level 7 seismic fortification intensity ensured;
- 99.995% power SLA guaranteed;
- All-year 7*24 Service Desk standing by
Power supply system:
- A full redundancy power supply system based on GE overall solution;
- TWO 3600KVA power supply lines separately connected into two distribution cabinets located at the two sides of the SH2;
- 2N power supply plus UPS units in isolated configuration, with host machine isolated from battery packs, to secure system stability;
- 30 minutes full load UPS operation solely powered by battery packs;
- N+1 backup outdoor diesel power generators;
- 12-hour full load operation of diesel generators ensured by underground oil tank;
Cooling System:
- STULZ high precision air-conditioners specially designed for computer rooms;
- Built according to the latest international DC construction standards, Design Specifications on Electronic Information Computer Rooms (GB50174);
- 1KW~1.5KW cooling capacity per square meter ensured by every air-conditioner safeguarded with double-compressors and double-power-supply configuration;
- Water-cooling down-draft ventilation design, with cold air ducts isolated from hot air ducts, to improve cooling effectiveness and energy utilization rate;
Fire Protection System:
- VESDA (Very Early Smoke Detection Apparatus) secured;
- IG541 environment-friendly fire-suppressant gas;
- Fire Protection System integrated in local area fire protection system;
Security System:
- Validity of every entrance into the IDX is ensured with metal detectors and ID checking system;
- Validity of every operation carried out by any visitor is ensured with access control system and video surveillance system in every zone;
- ID verification in special zones is ensured with biological recognition system, e.g. palm-print scanner;
- Basic security systems integrated in the overall local area security system (Languang Hi-Tech Park Security System);
- All doors/exits under the monitoring of access control and video surveillance systems;